The Must EH55-H3KS Tower UPS is a 3KVA/3KW high-frequency double-conversion online UPS in tower format — high efficiency, DSP digital control, and robust battery support for critical loads.
Model: EH55-H3KS
Rated Capacity: 3KVA / 3KW
INPUT
Input connection type: L+N+PE
Rated input voltage: 208 / 220 / 230 / 240 VAC
Voltage range: 110–300 VAC
Frequency range: 50/60 Hz (default), ±10 Hz (settable)
Input power factor: ≥ 0.99
Input THD: ≤ 4% (linear load)
OUTPUT
Output connection type: L+N+PE
Output voltage: 208 / 220 / 230 / 240 VAC
Output accuracy: ±1%
Output frequency: mains mode — same as AC; battery mode — 50/60Hz ±0.1%
Output THD: ≤2% (linear load); ≤4% (non-linear load, PF=0.7)
Output power factor: 1.0
OVERLOAD CAPACITY
AC mode: 30min @ 102–110% ; 10min @ 110–130% ; 30s @ 130–150% ; 200ms @ >150%
Battery mode: 10min @ 102–110% ; 1min @ 110–130% ; 10s @ 130–150% ; 200ms @ >150%
TRANSFER TIME
AC → battery: 0 ms
Inverter → bypass: 4 ms
AC priority mode: Supported
EFFICIENCY
AC Mode (Full Load): 95.5% @ 220VAC
Battery Mode (Full Load): 91.5% @ Rated Battery Voltage
BATTERY
Battery type: Lead Acid Battery
Rated battery voltage: 96VDC
Battery spec: 8 × 12V / (96VDC)
Number of internal batteries: 8
Charging current: 1A default (adjustable 1–2A)
Charging mode: Two-stage / Three-stage
DISPLAY & INTERFACE
LCD 2×8; 4 buttons + 4 LEDs; RS-232; USB; optional SNMP/RS485; EPO optional
ENVIRONMENTAL & MECHANICAL
Operating temp: 0 ~ 40°C; Humidity: 20–95% (no condensation)
Storage temp: -15 ~ 60°C (battery: 0 ~ 40°C)
Altitude: ≤1000m (derating above 1000m; up to 4000m IEC62040)
Noise: ≤45 dB
Machine dimensions (W×H×D): 438 × 88 × 504 mm
Package dimensions: 635 × 193 × 560 mm
Net weight: 20.5 kg
Gross weight: 22 kg
WARRANTY
1 year